TA SDR 11

T-piece with spigot, SDR 11

T-piece TA SDR 11 with spigot

  • Gas, water and H2
  • Maximum pressure: Gas 10 bar, Water 16 bar
  • Material: PE 100
  • Spigot
  • Safety technology
  • DVGW test mark: DV-8601AU2248 and DV-8606AU2249
Go back Data sheet

With extra long outlet spigot

With extra long outlet spigot

Reference d B D h L L1 t t1 z Weight kg BX PU
616685 20/20 42 29 17 77 95 31 45 8 0,040 200 3200
616338 25/25 54 36 19 108 110 41 66 13 0,080 50 900
615719 32/32 61 44 22 116 131 39 80 19 0,120 35 630
615720 40/40 70 53 25 146 151 43 88 30 0,210 25 450
615721 50/50 80 67 29 175 186 49 110 38 0,358 15 270
615722 63/63 94 81 33 197 203 56 125 42 0,530 10 180

FRIALEN safety fittings can be fused with SDR11 - SDR17.6 pipes.

Minimum wall thickness s minimum ≥ 3 mm.

Other levels of SDR can be processed on request.

Please note the mandatory labels directly on the product.

DVGW test mark issued: DV-8601AU2248 and DV-8606AU2249.

Dimension B = Diameter D with contact pin

With standard outlet spigots

With standard outlet spigots

Reference d B D h L L1 t t1 z Weight kg BX PU
616677 90/90 126 116 43 280 219 79 79 61 1,250 12 96
616680 110/110 148 141 48 310 247 82 82 73 1,950 6 48
616684 160/160 205 203 45 390 326 98 98 97 4,950 3 24
1 617175 180/180 228 223 49,9 495 389 105 87 143 7,960 2 16
2 617179 200/200 250 247 50,3 540 425 112 112 158 10,550 1 8
1 617183 225/225 281 278 61,2 590 469 120 120 175 14,700 1 8
1 Available from Q1 / 2024
2 Available from Q3 / 2024

FRIALEN safety fittings can be fused with SDR11 - SDR17.6 pipes.

Minimum wall thickness s minimum ≥ 3 mm.

Other levels of SDR can be processed on request.

Please note the mandatory labels directly on the product.

DVGW test mark issued: DV-8601AU2248 and DV-8606AU2249.

Dimension B = Diameter D with contact pin

Areas of Application

The FRIALEN-T pieces TA are used for pipe outlets of HD-PE pipelines.

Assembly Instructions

The fusion of the pipe ends with the FRIALEN-TA takes place by FRIALEN-fusing – leakproof and longitudinally strong.

The pipe ends are prepared (removing the oxide layer/cleaning) according to the general installation instructions (see “Assembly Instructions” for “FRIALEN-Safety Fittings for house connections and distribution pipes up to d 225”).

Good reasons for using the FRIALEN-TA:

  • Large coupler depth for ease of pipe guiding (no holding clamps required)

  • At dim. up to d 63, Length of outlet spigot dimensioned for two fusion operations

  • Extra wide fusion zones

  • Maximum stability through great wall thickness

  • Cold zones at the front side and in the middle of the coupler

  • Exposed heating coil for direct heat transmission to the pipe

  • Small annular gap for build-up of optimum joining pressure in the fusion zone

  • Touch proof electric contacts

  • Durable batch marking

  • Individually wrapped for dirt protection

  • Additional barcode for tracing back the fitting (Traceability-Coding)

Downloads