UB SDR 7,4

Coupler without inner stop, SDR 7.4

Coupler UB SDR 7.4 without inner stop

  • Water
  • Maximum pressure: 25 bar
  • Material: PE 100
  • Safety technology
  • Large insertion depth for good pipe routing (no holding devices required)
  • Separate fusion zone from d 280
  • DVGW test mark: DV-8606AU2249 and DV-8611AU2250
  • FM Approvals Class: 1613 (d 90 - d 355)

Note:

From nominal size 280 with preheating technology and separate fusion zone.

Go back Data sheet

PE 100 SDR 7.4

Maximum permissible working pressure 25 bar (water)

Reference d SDR range B D h L t Weight kg BX PU
616270 90 7,4 - 11 127 117 38 138 69 0,530 30 240
616271 110 7,4 - 11 152 142 50 159 79 0,870 24 192
616272 125 7,4 - 11 169 160 45 172 86 1,230 16 128
616273 140 7,4 - 11 187 181 51 184 92 1,640 12 96
616274 160 7,4 - 11 212 206 59 203 101 2,360 8 64
616282 180 7,4 - 11 225 225 63 210 105 2,700 6 48
616283 200 7,4 - 11 250 250 67 224 112 3,610 2 36
616284 225 7,4 - 11 280 280 73 240 120 4,900 1 33
616285 250 7,4 - 11 315 315 68 246 123 6,700 1 24
616286 280 7,4 - 11 355 355 84 268 134 9,300 1 18
616287 315 7,4 - 11 400 400 80 285 142 12,100 1 18
616288 355 7,4 - 11 450 450 88 300 150 16,700 1 9

From d 280 with preheating bar code to compensate for a larger annular gap.

FRIALEN safety fittings UB SDR 7.4 can be fused with SDR level 7.4-11 pipes. Other levels of SDR can be processed on request.

Please note the mandatory labels directly on the product.

DIN EN 12007-2

DVGW test marks issued: DV-8606AU2249 and DV-8611AU2250.

Areas of Application

The FRIALEN-Couplers UB SDR 7.4 and UB SDR 9 are used for pipe connections when laying long runs. Additional areas of application:

  • Integration of adapters into an existing pipeline
  • Connection of pipelines with fixed or restraint points

Assembly Instructions

The fusion of pipe ends with the FRIALEN-Coupler UB SDR 7.4 or UB SDR 9 takes place using FRIALEN-fusing – leakproof and longitudinally strong.

The pipe ends are prepared according to the general installation instructions (see “Assembly Instructions” for “FRIALEN-Safety Fittings for house connections and distribution pipes up to d 225” and “FRIALEN-Special Technology for laying large pipes and relining pipe networks”). This involves removing the oxide skin and cleaning the pipe ends. Please note that spigot of valves must be at least half as long as the coupler.

For removal of the oxide layer, FWSG scraper tools are available which facilitate a uniform swarf removal and a reproducible quality of the fusion area preparation.

To compensate a larger annular gap (> 1 mm, max.

3 mm) between coupler and pipe, the pre-heating barcode can be used for couplers UB SDR 7.4, d 280 - d 355 and couplers SDR 9, d 400 - d 630 (see instructions packed up with the coupler).

Good reasons for using the FRIALEN-Slide-over Coupler SDR 7.4 or SDR 9:

  • Large coupler depth for ease of pipe guiding (no holding clamps required)

  • Extra wide fusion zones

  • Maximum stability through great wall thickness

  • Cold zones at the front side and in the middle of the coupler

  • Exposed heating coil for direct heat transmission to the pipe

  • Small annular gap for build-up of optimum joining pressure in the fusion zone

  • Contacts safe to touch

  • Fusion indicators for visual fusion control

  • From d 180: External reinforcement for an ideal fusion pressure

  • From d 280: unique pre-heating technique for a optimal gap-bridging

  • Durable batch marking

  • Individually wrapped for dirt protection

  • Additional barcode for tracing back the fitting (Traceability-Coding)

Downloads